For commerical buildings the tables below summarize the prescriptive paths in chart form and some additional requirements to be noted in the following bullets:

  • For commercial buildings and residential buildings over three stories in height the building must comply with the energy efficiency requirements set forth in Chapter 5 of the 2006 IECC or ASHRAE/IESNA 90.1.
  • Section 502.3.1 allows buildings up to 40% of the window area to gross above grade wall area. Buildings that excceed this level are to use ASHRAE 90.1-2004 or section 506.

Source: IECC 2006 Table 502.3
Building DevelopmentRequirements: Fenestration

Climate Zone

1

2

3

4 Except Marine

5 and Marine 4

6

7

8

Vertical Fenestration (40% maximum of above-grade wall)

U-Factor

Framing materials other than metal with or without metal reinforcement of cladding

U-Factor

1.2

0.75

0.65

0.4

0.35

0.35

0.35

0.35

Framing with or without thermal break

Curtain Wall/Storefront U-Factor

1.2

0.7

0.6

0.5

0.45

0.45

0.45

0.45

Entrance Door U-Factor

1.2

1.1

0.9

0.85

0.8

0.8

0.8

0.8

All other U-Factor

1.2

0.75

0.65

0.55

0.55

0.55

0.5

0.5

SHGC-All Frame Types

SHGC: PF < 0.25

0.25

0.25

0.25

0.4

0.4

0.4

NR

NR

SHGC: 0.25 < PF < 0.5

0.33

0.33

0.33

NR

NR

NR

NR

NR

SHGC > 0.5

0.4

0.4

0.4

NR

NR

NR

NR

NR

Skylights (3% Maximum)

Glass

U-Factor

1.6

1.05

0.9

0.6

0.6

0.6

0.6

0.6

SHGC

0.4

0.4

0.4

0.4

0.4

0.4

NR

NR

Plastic

U-Factor

1.9

1.9

1.3

1.3

1.3

0.9

0.9

0.9

SHGC

0.35

0.35

0.35

0.62

0.62

0.62

NR

NR


Source: IECC 2006 Table 502.2(1)
Building Envelope Requirements: Opaque Assemblies

Climate Zone

1

2

3

4 Except Marine

5 and Marine 4

6

7

8

Roofs

Insulation entirely above deck

R-15ci

R-15ci

R-15ci

R-15ci

R-20ci

R-20ci

R-25ci

R-25ci

Metal Buildings (with R-5 thermal blocks)a,b

R-19 +
R-30

R-19

R-19

R-19

R-19

R19

R-19 +
R-30

R-19 +
R-30

Attic and Other

R-30

R-30

R-30

R-30

R-30

R-30

R-38

R-38

Walls, Above Grade

Mass

NR

NR

R-5.7cic,e

R-5.7cic

R-7.6ci

R-9.5ci

R-11.4ci

R-13.3ci

Metal Buildingb

R-13

R-13

R-13

R-13

R-13 +
R-13

R-13 +
R-13

R-13 +
R-13

R-13 +
R-13

Metal Framed

R-13

R-13

R-13

R-13

R-13 +
R-3.8ci

R-13 +
R-3.8ci

R-13 +
R-7.5ci

R-13 +
R-7.5ci

Wood Framed and Other

R-13

R-13

R-13

R-13

R-13

R-13

R-13

R-13 +
R-7.5ci

Walls, Below Grade

Below Grade Wall

NR

NR

NR

NR

NR

NR

R-7.5ci

R-7.5ci

Floors

Mass

NR

R-5ci

R05ci

R-10ci

R-10ci

R-10ci

R-15ci

R-15ci

Joist/Framing

NR

R-19

R-19

R-19

R-19

R-30

R-30

R-30

Slab-on-Grade Floors

Unheated Slabs

NR

NR

NR

NR

NR

NR

NR

NR

Heated Slabs

R-7.5 for
12in. below

R-7.5 for
12in. below

R-7.5 for
12in. below

R-7.5 for
12in. below

R-7.5 for
12in. below

R-7.5 for
36in. below

R-7.5 for
36in. below

R-7.5 for
36in. below

Opaque Doors

Swinging

U-0.7

U-0.7

U-0.7

U-0.7

U-0.7

U-0.7

U-0.7

U-0.5

Roll-up or Sliding

U-1.45

U-1.45

U-1.45

U-1.45

U-1.45

U-0.5

U-0.5

U-0.5

  • Thermal blocks are a minimum R-5 of rigid insulation, which extends 1-inch beyond the width of the purlin on each side, perpendicular to the purlin.
  • Assembly descriptions can be founf in Table 502.2.
  • R-5.7ci may be substituted with concrete block walls complying with ASTM c90, ungrouted or partially grouted at 32 in. or less on center vertically and 48 in. or less on center horizontally, with ungrouted cores filled with material having a maximum thermal conductivity of 0.44 Btu-in./h-f F.
  • When heated slabs are placed below grade, below grade walls must meet the exterior insulation requirements.
  • Insulation is not required for mass walls in Climate Zone 3A located below the "Warm-Humid" line, and in Zone 3B.